← Product page Quote via WhatsApp
TECTULby IMR
Fittings and couplings · Grounding accessories
TECHNICAL DATA SHEET
FT-TC-RAC-PIN-ESTATICA-001
Issue date: August 5, 2026 · Rev. 001
Check the current version

Bronze static grounding pin, 3/8 UNC thread — grounding for networks and equipment

TECTUL · Dispatch across Colombia · Exports to Central & South America

Threaded bronze pin, a connection point for a grounding cable or clamp on networks, tanks or equipment where static charge must be dissipated (for example, when transferring fuels or flammable liquids). The actual thread is 3/8 UNC (unified coarse), confirmed by the product's commercial sheet; the available manufacturer sheet's standard template generically cites NPT/ASME B1.20.1, which does not apply to this part — a grounding pin is not a fluid-conveyance fitting and its thread follows the usual UNC convention for this type of hardware, not the tapered NPT thread.

Bronze static grounding pin, 3/8 UNC thread — grounding for networks and equipment
Actual thread (corrects the source sheet's template)
3/8 UNC — confirmed in the product sheet, NOT NPT
the source sheet cites NPT generically; it does not apply to this pin
Dimension
L 39.0 mm · C 16.0 mm · 45 g
single size, per manufacturer sheet
Function
Connection point for grounding cable/clamp
dissipates static charge during flammable liquid transfer
Material
Brass bronze
not a fluid-conveyance fitting

Important: Before using these data in engineering, design or installation decisions on systems exposed to mechanical, pressure, rupture, fatigue, impact or water-hammer risk, it is essential to read the technical notice and limitation of liability at the end of this sheet.

SKU VT-59167 (3/8 UNC grounding pin) · sold by the unit

1. Technical specifications

ProductThreaded bronze pin, a connection point for a grounding cable or clamp
MaterialBrass bronze
Thread3/8 UNC (unified coarse) — confirmed in the product's commercial sheet; NOT NPT thread despite the available manufacturer sheet's standard template mentioning it generically
DimensionsL (length) 39.0 mm · C (diameter/head) 16.0 mm · weight 45 g
ApplicationNetworks, tanks or equipment requiring static charge dissipation, typically during fuel or flammable liquid transfer

The source manufacturer sheet reuses for this pin the same "NPT threaded connection per ANSI/ASME B1.20.1" box used across the whole threaded bronze fitting series; that box does not apply here. This sheet documents the actual thread (3/8 UNC) confirmed by the product's commercial sheet.

2. Frequently asked questions

Is this pin's thread NPT?

No. It is 3/8 UNC (unified coarse), confirmed by the product's commercial sheet. The available manufacturer sheet's standard template mentions NPT generically, but it does not apply to this part.

What is a grounding pin used for?

As an anchor point for a grounding cable or clamp on networks, tanks or equipment, to dissipate the static charge that builds up when transferring liquids —especially flammable ones— and reduce spark risk.

3. Application notes

Feasibility

Suitable as a grounding point on liquid-transfer networks, tanks and equipment, especially for flammable liquids. It is not a fluid-conveyance fitting: it has no internal flow passage.

Installation

Thread with 3/8 UNC into the designated point on the equipment or network; connect the grounding cable or clamp ensuring good electrical contact, free of paint or rust on the contact surface.

Design

Selecting the grounding system (maximum allowable resistance, number of points) is the designer's responsibility per the applicable electrical code (NTC 2050/RETIE in Colombia or other); this pin is only the mechanical connection point.

4. Technical notice and limitation of liability

The pressures, dimensions, weights and other characteristics in this sheet are theoretical calculation values obtained from nominal properties published in the standards cited (ASME B36.10-2022, ASME B31.3-2024, ASTM A106/A106M-19a, ASTM A53/A53M-24, API Spec 5L 46th ed.). They guide selection; they are not a certificate of conformity for any given lot.

The actual behavior of each lot varies with manufacturing — wall tolerance (up to −12.5%), out-of-roundness, residual stresses — and with the raw material — chemical composition within the ranges the standard allows, heat-to-heat differences. To certify a lot, the tests defined by its product standard are required: tensile test, flattening test and hydrostatic test, documented in the manufacturer's mill test certificate (MTC), which TECTUL supplies upon request; testing of the lot in an independent laboratory can also be arranged.

These values must not be used as the sole criterion in critical or safety applications, or wherever failure of the line may compromise people, property or the environment: in such cases the design belongs to the project's responsible engineer under the applicable code (ASME B31.3, B31.1 or the one governing the installation), with the design temperature, corrosion allowance and load cases of the actual service. Before deciding with these data, consult our technical team.

Sources

This data sheet is the property of TECTUL, part of the Industrias IMR group. Reproduction without attribution is prohibited. Original document and updates: tectul.com/en/conduccion-de-fluidos/racores-y-acoples/ficha-tecnica-pin-de-estatica.

Check the current version
TECTUL · FT-TC-RAC-PIN-ESTATICA-001 · Rev. 001 · August 5, 2026WhatsApp +573161111666