Enclosed Direct-On-Line Starter

Enclosed direct-on-line (DOL) starter with contactor, thermal overload relay and integrated pushbutton station, ready to install. Quoted according to motor power and voltage.

Availability
Quote
Family
Control & automation
Line
Industrial
Response
Same business day
Enclosed Direct-On-Line Starter
Product quoted on request

Tell us the reference or key specification (current, power, gauge, size), quantity and city — a technical advisor sends your quote the same business day.

01Technical description

A direct-on-line (DOL) starter applies full voltage to the motor through a contactor and overload relay in an enclosure with pushbuttons, per IEC 60947-4-1. On starting, the motor draws 6 to 8 times its rated current, so DOL is used where the supply and the driven machine tolerate that inrush.

The enclosed direct-on-line starter, also called DOL, brings together in one enclosure the basic elements for starting and protecting a motor: contactor, thermal overload relay and control pushbuttons. At TECTUL it is quoted by motor power, motor voltage, rated current, enclosure type and installation conditions. The actual lot data confirms a ready-to-install solution with contactor, thermal overload relay and integrated pushbutton station. It differs from a three-pole contactor because it is not only the switching component; it is an assembled set for local motor control. It also differs from a soft starter because it applies direct voltage to the motor, without an electronic acceleration ramp. IEC 60947-4-1 is a reference for motor starters, while machine wiring should consider IEC 60204-1 criteria.

Selection guide

  • Send motor power, rated current and voltage.
  • Indicate whether control will be local, remote or combined.
  • Define the environment type to select the suitable enclosure and protection.
  • Confirm whether pushbuttons, selector switch, pilot light, emergency stop or terminal blocks are required.
  • Validate whether direct-on-line starting is acceptable for the network and machine mechanics.

Mounting recommendations

  • Fix the enclosure on a firm, accessible surface protected from the environment.
  • Connect supply, motor and ground according to the diagram of the supplied assembly.
  • Set the thermal overload relay to the motor rated current.
  • Test rotation direction and stop function before continuous operation.
  • Label the pushbutton station and circuit for maintenance intervention.

We dispatch enclosed direct-on-line starters to Bogotá, Medellín, Cali, Barranquilla and all of Colombia. Request a quote via WhatsApp with the motor nameplate and installation environment.

Full-load current of three-phase motors (NTC 2050, table 430-150)

Power220–230 V440–460 V
1 HP4.2 A2.1 A
5 HP15.2 A7.6 A
10 HP28 A14 A
25 HP68 A34 A
50 HP130 A65 A

Values from table 430-150 of NTC 2050 (Colombian Electrical Code; equivalent to NEC Table 430.250) for squirrel-cage induction motors. These values size the contactor, overload relay and conductors of the starter.

02Frequently asked questions

What is the price of an enclosed direct-on-line starter?

It depends on power, voltage, current, enclosure type and control accessories. TECTUL quotes via WhatsApp with the motor nameplate.

What is the difference between an enclosed direct-on-line starter and a soft starter?

The direct-on-line starter energizes the motor directly. The soft starter uses electronics to reduce starting and stopping stress.

How is an enclosed direct-on-line starter installed?

The enclosure is fixed, supply, motor output and grounding are connected, and the thermal overload relay is adjusted. The supplied equipment diagram must be followed.

What does it normally include?

According to the actual lot data, it includes contactor, thermal overload relay and integrated pushbutton station. Additional accessories are confirmed when quoting.

Is it suitable for pumps?

Yes, provided the motor accepts direct-on-line starting and the network supports starting current. Power, voltage and application must be validated.

When is direct-on-line starting not recommended?

When starting current or mechanical shock affects the network, pump, transmission or process. In those cases a soft starter or VFD is evaluated.

How much current does a 10 HP motor draw at 440 V?

14 A at full load per table 430-150 of NTC 2050; on direct-on-line starting the inrush reaches 84–112 A (6 to 8 times rated) during acceleration.

Up to what power is DOL starting acceptable?

There is no fixed HP limit: the criterion is whether the supply and the load tolerate the 6-to-8-times inrush. When voltage dip or mechanical shock is unacceptable, move to a soft starter or a VFD.