Three-pole contactor for switching motors and three-phase loads, with 110/220/440 V coil as required. Quoted by current rating (9 A to 95 A) and auxiliary contact accessories.

Tell us the reference or key specification (current, power, gauge, size), quantity and city — a technical advisor sends your quote the same business day.
A three-pole contactor is an electromagnetic switching device for three-phase loads, built to IEC 60947-4-1. It is selected by AC-3 current rating (9 A to 95 A in this line), coil voltage (110/220/440 V) and the utilization category of the load.
The three-pole contactor is the switching device used to connect and disconnect motors, pumps, fans, heaters and other three-phase loads from a control circuit. At TECTUL it is quoted by industrial line according to operating current, coil voltage, utilization category and control accessories. The actual product description includes 110/220/440 V coils as required, currents from 9 A to 95 A and auxiliary contacts when the panel requires indication, interlocking or additional logic. Its selection must be distinguished from a manual motor starter/motor protection circuit breaker and from an overload relay: the contactor switches the load; the motor protection circuit breaker protects and provides isolation; the overload relay trips on prolonged overload when coupled to the contactor. For motor applications, the IEC 60947-4-1 standard family is used as a technical reference for contactors and motor starters.
We dispatch three-pole contactors to Bogotá, Medellín, Cali, Barranquilla and all of Colombia. Request a quote via WhatsApp with voltage, current, application and required accessories.
| AC-3 current | Three-phase motor at 440 V |
|---|---|
| 9 A | 4 kW |
| 12 A | 5.5 kW |
| 18 A | 7.5 kW |
| 25 A | 11 kW |
| 32 A | 15 kW |
| 40 A | 18.5 kW |
| 50 A | 22 kW |
| 65 A | 30 kW |
| 80 A | 37 kW |
| 95 A | 45 kW |
Correspondence published in IEC manufacturer catalogs for utilization category AC-3 at 415–440 V. The relevant IEC 60947-4-1 utilization categories are: AC-1 (non-inductive or slightly inductive loads such as resistance heating), AC-3 (squirrel-cage motors: making at 6 times rated current, breaking with the motor running) and AC-4 (inching and plugging: making and breaking at 6 times rated current).
The price depends on current, coil voltage, utilization category and accessories. At TECTUL we do not publish generic values; request a quote via WhatsApp with the motor or load data.
The three-pole contactor switches the load through a control coil. The manual motor starter/motor protection circuit breaker protects the motor against overload and short circuit and can act as a local isolator.
It is mounted on DIN rail or plate, with three-phase supply on the main poles, output to the load and the coil connected to the control circuit. It must be wired by qualified personnel.
Yes. The actual lot data includes 110/220/440 V coils as required. Confirm the control voltage before requesting a quote.
When the panel requires indication, electrical interlocking, seal-in control, alarm or integration with timers, control relays or PLCs.
Yes, but selection changes by utilization category. For three-phase motors, operating current and duty are validated; for heaters, the load and switching type are reviewed.
AC-3 per IEC 60947-4-1: it covers making the squirrel-cage motor at 6 times its rated current and breaking with the motor running. AC-4 is specified only for frequent inching or plugging duty.
A 32 A contactor in category AC-3, per the correspondence in IEC manufacturer catalogs. Always confirm the motor nameplate current before requesting a quote.
Updated: July 22, 2026