Three-Pole Contactor
Product quoted on request

Tell us the reference or key specification (current, power, gauge, size), quantity and city — a technical advisor sends your quote the same business day.

01Technical description

A three-pole contactor is an electromagnetic switching device for three-phase loads, built to IEC 60947-4-1. It is selected by AC-3 current rating (9 A to 95 A in this line), coil voltage (110/220/440 V) and the utilization category of the load.

The three-pole contactor is the switching device used to connect and disconnect motors, pumps, fans, heaters and other three-phase loads from a control circuit. At TECTUL it is quoted by industrial line according to operating current, coil voltage, utilization category and control accessories. The actual product description includes 110/220/440 V coils as required, currents from 9 A to 95 A and auxiliary contacts when the panel requires indication, interlocking or additional logic. Its selection must be distinguished from a manual motor starter/motor protection circuit breaker and from an overload relay: the contactor switches the load; the motor protection circuit breaker protects and provides isolation; the overload relay trips on prolonged overload when coupled to the contactor. For motor applications, the IEC 60947-4-1 standard family is used as a technical reference for contactors and motor starters.

Selection guide

  • Confirm the rated current of the motor or load and do not select only by commercial horsepower.
  • Define a coil voltage compatible with the panel control circuit.
  • Validate the utilization category: motors, heaters and mixed loads do not require the same contactor.
  • Request auxiliary contacts if you need run, stop, fault or interlock signals.
  • Indicate whether the contactor will be used with an overload relay, motor protection circuit breaker, timer or enclosed starter.

Mounting recommendations

  • Install inside a panel with ventilation and space for heat dissipation.
  • Tighten terminal torque according to the datasheet of the supplied equipment manufacturer.
  • Separate power and control wiring to reduce electrical noise in coils and signals.
  • Verify actual coil voltage before energizing to prevent humming, dropout or burnout.
  • Label inputs, outputs and auxiliaries for industrial maintenance.

We dispatch three-pole contactors to Bogotá, Medellín, Cali, Barranquilla and all of Colombia. Request a quote via WhatsApp with voltage, current, application and required accessories.

Current-to-power equivalence in AC-3 (IEC 60947-4-1)

AC-3 currentThree-phase motor at 440 V
9 A4 kW
12 A5.5 kW
18 A7.5 kW
25 A11 kW
32 A15 kW
40 A18.5 kW
50 A22 kW
65 A30 kW
80 A37 kW
95 A45 kW

Correspondence published in IEC manufacturer catalogs for utilization category AC-3 at 415–440 V. The relevant IEC 60947-4-1 utilization categories are: AC-1 (non-inductive or slightly inductive loads such as resistance heating), AC-3 (squirrel-cage motors: making at 6 times rated current, breaking with the motor running) and AC-4 (inching and plugging: making and breaking at 6 times rated current).

02Frequently asked questions

What is the price of a three-pole contactor?

The price depends on current, coil voltage, utilization category and accessories. At TECTUL we do not publish generic values; request a quote via WhatsApp with the motor or load data.

What is the difference between a three-pole contactor and a manual motor starter?

The three-pole contactor switches the load through a control coil. The manual motor starter/motor protection circuit breaker protects the motor against overload and short circuit and can act as a local isolator.

How is a three-pole contactor installed in a panel?

It is mounted on DIN rail or plate, with three-phase supply on the main poles, output to the load and the coil connected to the control circuit. It must be wired by qualified personnel.

Can I order it with a 110, 220 or 440 V coil?

Yes. The actual lot data includes 110/220/440 V coils as required. Confirm the control voltage before requesting a quote.

When do I need auxiliary contacts?

When the panel requires indication, electrical interlocking, seal-in control, alarm or integration with timers, control relays or PLCs.

Is it suitable for motors and resistive loads?

Yes, but selection changes by utilization category. For three-phase motors, operating current and duty are validated; for heaters, the load and switching type are reviewed.

Which utilization category do I need for a standard three-phase motor?

AC-3 per IEC 60947-4-1: it covers making the squirrel-cage motor at 6 times its rated current and breaking with the motor running. AC-4 is specified only for frequent inching or plugging duty.

Which contactor suits a 15 kW motor at 440 V?

A 32 A contactor in category AC-3, per the correspondence in IEC manufacturer catalogs. Always confirm the motor nameplate current before requesting a quote.