Molded Case Circuit Breaker

Molded case circuit breaker (MCCB) for main protection of industrial panels. Quoted by current (15 A to 1600 A) and interrupting capacity.

Availability
Quote
Family
Electrical protection
Line
Industrial
Response
Same business day
Molded Case Circuit Breaker
Product quoted on request

Tell us the reference or key specification (current, power, gauge, size), quantity and city — a technical advisor sends your quote the same business day.

01Technical description

A molded-case circuit breaker (MCCB) used as a main is an automatic breaker per IEC 60947-2 or UL 489 protecting the panel feed against overload and short circuit. It is selected by rated current (15 A to 1,600 A in this line), ultimate breaking capacity Icu at service voltage, and number of poles.

The molded case circuit breaker, also known as an MCCB, is used as main or secondary protection in low-voltage industrial panels. Its function is to open the circuit under overcurrent and short-circuit conditions according to system coordination, so it must not be selected only by nominal amperage. Unlike a knife-blade safety switch, the molded case circuit breaker incorporates an automatic trip mechanism; and unlike a DIN rail circuit breaker, it is intended for feeders, main loads and panels with higher coordination requirements. To quote it, operating current, voltage, number of poles, required interrupting capacity, load type, mounting space, accessories, thermal or magnetic adjustment when applicable, and compatibility with panel busbars or cables are reviewed. TECTUL supplies it for construction, maintenance and replacement in industrial facilities that require reliable protection and technical selection.

Selection guide

  • Confirm design current, system voltage, phases and neutral if applicable.
  • Validate interrupting capacity with the short-circuit calculation at the installation point.
  • Define whether a shunt trip, auxiliary contact, extended handle or interlock is required.
  • Review panel dimensions, mounting type and connection method to busbars or cables.
  • Coordinate tripping with upstream protections and downstream branch circuits.

Mounting recommendations

  • Do not replace an MCCB with one of lower capacity without validating electrical coordination.
  • Respect orientation, clearance, terminal torque and ventilation indicated by the manufacturer.
  • Identify the protected circuit and leave access for operation and maintenance.
  • After mounting, verify continuity, tightening, heating and functional tripping when applicable.
  • Installation must comply with RETIE and NTC 2050 under the responsibility of qualified personnel.

We dispatch to Bogotá, Medellín, Cali, Barranquilla and all of Colombia. Request a quote via WhatsApp for your molded case circuit breaker with current, voltage, poles, required interrupting capacity and panel application.

Selection parameters (IEC 60947-2)

ParameterMeaning
InRated uninterrupted current of the breaker
IcuUltimate breaking capacity in kA: maximum fault current it can safely interrupt
IcsService breaking capacity (% of Icu): the breaker remains operable after interrupting it
IrThermal trip setting on adjustable frames
Commercial frames100 · 250 · 400 · 630 · 800 · 1600 A (manufacturer catalogs)

Industrial MCCBs are certified under IEC 60947-2 (IEC markets) or UL 489 (North American markets). The declared Icu must exceed the short-circuit current calculated at the installation point.

02Frequently asked questions

What is the price of a molded case circuit breaker?

It is quoted via WhatsApp because the value depends on current, number of poles, interrupting capacity, accessories, mounting type and industrial line availability.

What is the difference between a molded case circuit breaker and a DIN rail circuit breaker?

The molded case circuit breaker is used in feeders and higher-demand main or secondary protection. The DIN rail breaker is used in branch circuits and modular panels.

Is it the same as an industrial breaker?

In Colombian commercial usage it is often called an industrial breaker, but for quoting it is better to specify that an MCCB or molded case circuit breaker is required.

How is interrupting capacity selected?

It must be defined with the short-circuit calculation at the installation point and panel coordination. Selection by visual estimate is not recommended.

How should it be installed?

It must be fixed in a suitable panel, with compatible conductors or busbars, correct terminal torque, circuit identification and review by qualified personnel.

Can TECTUL supply it with accessories?

TECTUL can quote accessories according to the available line, such as auxiliary contacts, trip coils, handles or interlocks, if the project requires them.

What breaking capacity does my main breaker need?

Higher than the available short-circuit current at the installation point, calculated from the transformer and service impedance; usual commercial values run from 25 to 85 kA per IEC 60947-2.

When do I use an MCCB instead of a DIN-rail miniature breaker?

From about 100 A rated current, or when the available short circuit exceeds 10 kA: IEC 60898-1 miniature breakers top out at 63 A and 10 kA, while MCCBs cover up to 1,600 A with far higher breaking capacities.