TECTULby IMR
HomeIndustrial electricalTerminals & connectorsTubular Splice Connector

Tubular Splice Connector

Tubular compression connector for splicing copper power cables, insulatable with tape or heat-shrink tubing.

Availability
Quote
Family
Terminals & connectors
Line
Industrial
Response
Same business day
Tubular Splice Connector
Product quoted on request

Tell us the reference or key specification (current, power, gauge, size), quantity and city — a technical advisor sends your quote the same business day.

01Technical description

The tubular splice connector joins two copper cable ends butt-to-butt through a tinned-copper barrel crimped by compression, per UL 486A-486B. The finished splice is insulated with self-fusing tape or heat-shrink tubing until the cable's insulation level (600 V) is restored.

The tubular splice connector is a compression barrel used to join ends of copper power cables in repairs, extensions and electrical installations where mechanical and electrical continuity are required. Unlike the copper compression lug, it does not terminate the cable in an eye for a bolt; it joins cable to cable and must then be insulated according to the circuit service level. At TECTUL it is quoted for copper power splices, insulatable with tape or heat-shrink tubing according to the application. Correct selection depends on conductor gauge, cable type, space in the raceway or panel and available crimping tool. It should not be used as a substitute for an eye lug or as an improvised adapter for aluminum.

Selection guide

  • Select the connector according to copper conductor gauge and cable type.
  • Confirm whether the splice will remain in tray, box, panel, raceway or equipment.
  • Define the subsequent insulation system: electrical tape, self-fusing tape, heat-shrink tubing or another defined by the project.
  • Validate that the crimping tool and dies are compatible with the selected connector.

Installation recommendations

  • Cut cable ends cleanly and strip only the length required for the barrel.
  • Insert each conductor to the correct position before crimping.
  • Make the required compressions without displacing the cable inside the connector.
  • After crimping, verify mechanical firmness before insulating.
  • Insulate the splice according to environment, service voltage and project procedure.

We dispatch to Bogotá, Medellín, Cali, Barranquilla and all of Colombia. Request a quote via WhatsApp for your tubular splice connector indicating gauge, quantity and expected insulation type.

Compression splicing procedure

StepDetail
1. StrippingTo half the barrel length, without nicking the copper
2. InsertionEach cable to the center stop of the connector
3. CrimpingDie of the size; 2 or more compressions per side, from center outward
4. InsulationHeat-shrink with typical 3:1 shrink ratio (catalogs) or self-fusing tape + jacket tape
5. VerificationEmbossed die code and pull check

Splices per UL 486A-486B: the connector-die-tool system must be the one the manufacturer specifies so the joint keeps the conductor's ampacity.

02Frequently asked questions

What is the price of the tubular splice connector?

It is quoted via WhatsApp according to gauge, quantity and availability. We do not publish or invent prices for this industrial line.

What is a tubular splice connector used for?

It is used to join two ends of cable by compression, especially in repairs, extensions and power conductor splices.

How does it differ from a copper compression lug?

The tubular connector joins cable to cable; the copper compression lug terminates the cable in an eye to fasten it to a bolt or busbar.

How is the tubular connector installed?

The ends are stripped, inserted into the barrel, crimped with the correct die and then the splice is insulated according to the project procedure.

Is it suitable for aluminum cable?

It should not be assumed. This page focuses on splices for copper cables; for aluminum or transitions another compatible accessory must be validated.

What data should I send for a quote?

Cable gauge, number of splices, conductor type, installation location and whether you need a recommendation for subsequent insulation.

Crimped splice or screw connector?

Crimped for power: die-calibrated compression gives a permanent full-section joint that does not loosen under vibration or thermal cycles; screw connectors remain for accessible control taps.

How is a power splice insulated?

With heat-shrink tubing sized to the splice diameter (typical 3:1 shrink ratio) or with self-fusing rubber tape plus protective tape, rebuilding at least the original 600 V insulation level.