TECTULby IMR
HomeIndustrial electricalGroundingComplete Grounding Kit

Complete Grounding Kit

Complete kit: Copperweld rod, connector, bare copper cable, conductive cement and inspection box. Quoted according to design.

Availability
Quote
Family
Grounding
Line
Industrial
Response
Same business day
Complete Grounding Kit
Product quoted on request

Tell us the reference or key specification (current, power, gauge, size), quantity and city — a technical advisor sends your quote the same business day.

01Technical description

The grounding kit gathers the components of a complete electrode: copperweld rod, connector, bare copper conductor, ground-enhancement compound and inspection box, to comply with NTC 2050 article 250 and RETIE. The design target is a maximum of 25 Ω per single electrode (NTC 2050, 250-84).

TECTUL's complete grounding kit brings together the main components to execute a grounding point according to design: Copperweld rod, connector, bare copper cable, conductive cement and inspection box. It is a practical purchasing solution when the project does not require each component to be acquired separately or when maintenance needs to replace a complete point with material traceability. It differs from the Copperweld rod page because here only the electrode is not quoted; conductor, connection, soil enhancer and inspection access are also considered. It differs from conductive cement because the enhancer is only one of the elements in the assembly. The final composition must be confirmed with drawings, conductor gauge, rod length, box type, soil conditions and the electrical responsible party's criteria; therefore it is quoted according to design and not with a published fixed price.

Actual lot dataAvailable specification
Sales unitQuotation by industrial line
Mentioned componentsCopperweld rod, connector, bare copper cable, conductive cement and inspection box
Quotation criterionAccording to design

Installation recommendations

  • Check that the kit corresponds to the electrical drawing and not only to a generic material list.
  • Confirm cable gauge, rod length and connector type before purchasing.
  • Install the inspection box at an accessible point for measurement and maintenance.
  • Use conductive cement only when the design or soil condition justifies it.
  • Record final measurements and point location for future inspections.

We dispatch to Bogotá, Medellín, Cali, Barranquilla and all of Colombia. Request a quote via WhatsApp for the complete grounding kit by sending drawing, quantities and delivery city.

Kit components and their normative role

ComponentFunction
Copperweld rod ≥2.4 mGrounding electrode (RETIE)
Rod-to-cable connectorQualified bond of conductor to electrode (UL 467)
Bare copper conductorElectrode conductor to the ground bar
Enhancement compoundLowers soil resistivity (IEC 62561-7)
Inspection boxAccess for periodic measurement and maintenance

Resistance is verified with an earth tester by the fall-of-potential method; if the electrode exceeds 25 Ω, NTC 2050 requires additional electrodes spaced at least 1.8 m apart.

02Frequently asked questions

What is the price of the complete grounding kit?

It is quoted according to design, quantity and included components. TECTUL does not publish a fixed price because the kit may change by cable gauge, rod, box and accessories.

How does it differ from buying only the Copperweld rod?

The rod is the electrode. The complete kit groups rod, connector, bare copper cable, conductive cement and inspection box when the project requires them.

How is the grounding kit installed?

It is installed according to the electrical drawing: electrode location, cable connection, enhancer application if applicable, inspection box and final system measurement.

What does the lot kit include?

The actual description mentions Copperweld rod, connector, bare copper cable, conductive cement and inspection box. The final composition is confirmed when quoting.

Is it suitable for industrial projects?

Yes, it can be used in industrial and commercial installations as long as the components match the grounding design and site measurements.

Does TECTUL dispatch to other cities?

Yes. TECTUL dispatches to Bogotá, Medellín, Cali, Barranquilla and other Colombian cities according to availability and transport conditions.

How is ground resistance measured?

With an earth tester using the fall-of-potential (three-point) method: two auxiliary stakes are driven in line and the electrode under test is measured — the measurement that supports the installation's RETIE certification.

Is a single electrode enough?

Only if it measures 25 Ω or less (NTC 2050, 250-84); otherwise electrodes are added in parallel, spaced at least 1.8 m apart, until the design value is met.

03Related products

Need another electrical reference? We carry the full industrial lines of the catalogs we distribute — if the equipment or material you need is not published, we quote it anyway. Quote via WhatsApp

Updated: July 22, 2026